72
Figure 55 Correct and incorrect cable binding
Route different types of cables (for example, power cables and signal cables) separately. If they
are close to one another, cross them over one another. If you route them in parallel, make sure the
space between a power cable bundle and a signal cable bundle is at least 30 mm (1.18 in).
The cable management brackets and cable routing slots, inside or outside the rack, are smooth
and have no sharp edges or tips.
When you route cables through sharp sheet metal penetration points or along sharp edges of
mechanical parts, use bushings or take any other action to protect the cables from being cut or
abraded. The sheet metal penetration points must be smooth and fully rounded.
Use the correct type of ties to bind the cables. Do not bind cables with joined ties. The following
types of ties are available: 100 × 2.5 mm (3.94 × 0.10 in), 150 × 3.6 mm (5.91 × 0.14 in), 300 ×
3.6 mm (11.81 × 0.14 in), 530 × 9 mm (20.87 × 0.35 in), and 580 × 13 mm (22.83 × 0.51 in).
After binding the cables, cut the excess from the ties, leaving no sharp or angular tips. See Figure
56.
Figure 56 Cutting cable ties
When you bend cables, bind them as shown in Figure 57. To avoid excessive stress causing cable
core break, do not tie up the cables in the bending area.